Skip to Content
LGS Solutions
LGS Solutions · Engineering model

Rainscreen Vent Lab

Set the wind, the vents, the storey height and the cavity gap, and watch what the cavity's air does to the water at a Nichiha EX joint. The pressures and the water's height come from a physics model; the moving drops show the path.

  1. Pick a scenario or set the wind, the vents and the compartment.
  2. Watch the joint at the gust: drag the time bar to freeze any moment.
  3. Read the result and the sweeps. Tap i beside anything for what it means.
WORKINGModelled, not testedRunning the first case…
Scenarios: tap to switch on or off
Wind
Wind
Pa
About a 23 m/s gust on a windward wall.
Pa
s
4,000 Pa/s. Field gusts: about 4,000 Pa/s.
Vents at the story breaks

One row of holes or slots in Nichiha's aluminium profile; untick a vent to block it.

1,695mm²/m
mm c/c
76.3 mm² each, 22.2 per metre; closest centres 20 mm.
1,181mm²/m
mm c/c
1,695 mm²/m per row; through both rows and the 7 mm outlet 1,181. Closest centres 20 mm.
One row of slots gives at most 3,814 mm²/m (20 mm apart), 2,516 through the J-channel's path.
Cavity
Behind the cavity
m
One LGS storey: 2.8 m. Two storeys: 5.6 m.
mm
LGS: 15 mm (JE825 clip). Nichiha: at least 12 mm.
Joint
Seal strip at this joint
°
Not published; 60° assumed.
More inputs: leaks, rain, board stiffness
%/m
Estimate: 4 %/m at low-rise heights.
mm²/m²
Estimate.
L/(s·m²)
Air-barrier assembly limit: 0.2.
mm/h
°C
Sharp-edged hole in thin sheet: 0.61.
GPa
Estimate.
GPa
Estimate.

01 · The joint in section

t = 0.00 s
air pressure: legend in the viewNichiha EX 16 mm2.4 mm PVC seal stripGlasroc X 9 mmwaterpathlines: moving airstud bay, not modelled

True scale: the tongue stands 15 mm above the shoulder, the slot is 1.6 mm wide. Colours are air pressure on one legend for the whole run, so a colour means the same pressure in every frame: the same colour either side of the joint means the cavity is keeping up. The strip on the left is the whole compartment, heights to scale, depths not; tap a joint to show it. Drops and pathlines move 12 times slower than life. In the cavity the pathlines move at the air speed the model computes; outside, the wind's turn and its eddies, and the dip the eddies put in the pressure, are illustrative. The water's film down the face follows the CFD runs, and so does the joint without its seal strip: air forces in from about 200 Pa; above about 275 Pa the bubble grows and, 0.14 to 0.17 s later, blows the water out and throws it across the cavity at the runs' speed; the joint stays open until the push falls. Wetter edges hold longer, drier ones blow sooner. The shapes are illustrative. Axes in millimetres; triad: X into the wall, Y up.

See the water in the joint solved by CFD, frame by frame ↓

02 · Pressure through the gusts

Joint

outsidecavitypush on the jointwhat the joint holds without its strip

03 · What each setting buys

Each point is a full run with everything else as you set it; the blue dot is where you are. Drying is the sun warming the cavity 5 K with no wind: air rising through the vents.

04 · Result

WORKING Modelled, not tested
JointUp (m)Push (Pa)Water (mm)Status

05 · The water, solved by CFD

Modelled, not tested

OpenFOAM interFoam (volume of fluid, a free-surface method) on the true EX joint, 60° contact angle, without and with the seal strip: the air coloured by the pressure it solved, the water blue. Each frame is the solver's own result, not a drawing. The contact angle on these edges is not published: at 75° the joint blew at 250 Pa (0.138 s); at 45° it held 250 Pa for the full 0.3 s and 290 Pa until 0.297 s. The other runs use 60°.

t = 0.010 s · 10× slower than life

165 Pa across the joint, 33 Pa over the 132 Pa the Lab's simple model gives. The water climbs the slot to the tongue's top and stops at its sharp corner for the whole 0.25 s: the corner pins the water surface. A chipped or dirty corner loses that, so the Lab keeps 132 Pa.

The wind moves the boards too: CalculiX with the CFD

The gust that pushes water up the joint also bows the boards. CalculiX shell models of a course on its clips and of the Glasroc X on its studs give the movement, and the CFD ran the joint as the wind shapes it. One JE825 clip holds both courses at a joint, so they move together: at 300 Pa the slot opens 0.02 mm, and even with a clip gone it closes only 0.05 mm (0.13 mm at a panel's end). Between studs the Glasroc X bows in about 1.7 mm per kPa of cavity pressure; the section above cuts there and shows it. None of this moves the moment water gets through by more than 0.005 s, no more than a finer mesh moved it: the joint keeps its shape in the wind.

The joint in the windSlot at 300 PaWater through, 280 Pa300 Pa
As drawn, not moving1.60 mm0.168 s0.140 s
Clipped1.62 mm0.166 s0.139 s
A clip gone, mid-panel1.55 mm0.173 s0.144 s
A clip gone, panel end1.47 mm0.164 s0.143 s
Clipped, cavity 0.9 mm deeper (Glasroc X bowed in)1.62 mmnot run0.139 s
CalculiX shell models at 1 kPa: a Nichiha course bowing between its clips; two courses bowing in together where the clip at their joint is gone; the joint at 300 Pa at true scale, clipped and with the clip gone; the Glasroc X bowing between its studs
CalculiX, 1 kPa of push: a course bows between the clips at its joints (red); with a clip gone, both courses at that joint swing in together; at 300 Pa the joint keeps its shape at true scale; the Glasroc X bows most halfway between studs (4.2 mm per kPa with nothing behind it, about 1.5 with the lining sealed). Moduli are estimates: Nichiha 5 GPa, Glasroc X 2.5 GPa.

06 · How to read this

The joint is a manometer; the cavity is a tank

A manometeroutside air, poutcavity air, pcavhpout − pcav = ρ g hThe EX joint works the same wayoutside air,poutcavity,pcavVhairlinelipslottongueh15mmspillsoverspills at pout − pcav = ρg·15 mm − meniscus pull = 147 − 15 = 132 Pa
The push through the joint, outside minus cavity pressure, lifts water up the slot until its weight balances the push: ρgh. A 15 mm tongue holds 147 Pa of water; the meniscus in the narrow gap pulls up by 2σcosθ/w, 15 Pa at a 60° contact angle, so at 132 Pa the water reaches the top and tips over a worn corner (a clean, sharp corner pins it longer: section 05). That is what "the lap alone holds" means: the joint with no seal strip. Where the 2.4 mm PVC seal strip is in place in the slot, water stops at the strip and the strip takes the push. Not to scale.
outside airptop higherpbottomwind growsup the walltop vent: J-channelbottom vent: startera joint feelspout − pcavcavity airpcavGlasroc X bows in:the tank grows,so more air mustflow inroomsmall leak
The vents are orifices filling a tank whose wall gives. A gust raises the outside pressure; air flows in through the vents until the tank catches up, and meanwhile every joint feels the gap. Big vents and a stiff wall make the tank quick: in the electrical analogue the vents are resistors, the tank a capacitor, and R·C the cavity's time constant. The two vents see different wind pressures, so the tank settles between them and the joints at the top and bottom of a tall compartment feel the difference.

Two tests

  • The lap alone, 132 Pa: where the seal strip is missing, the water reaches the top of the tongue at 132 Pa, and a chipped or dirty corner lets it into the cavity. A clean, sharp corner held it in the CFD until the air blew it out at 280 Pa (270 Pa held for 0.3 s). The contact angle is not published: at 45° the joint held 250 Pa for 0.3 s and 290 Pa until 0.297 s; at 75° it blew at 250 Pa. The Lab uses 60°. 132 Pa is the safe line for leaks.
  • With the seal strip in place and pressed on the lip, water stops at the strip (OpenFOAM, 240 Pa).

Taken as given (estimates)

  • Bending moduli: Glasroc X and lining 2.0 GPa, Nichiha 5.0 GPa. Neither maker publishes one. The boards bend as plates; each 470 mm course is held only by the clips at its two joints, so it bows both ways, 0.26 mm on average per kPa (CalculiX shell model).
  • The joint keeps its shape. The wind bows the panels, but one clip holds both courses at a joint, so they move together: the slot opens 0.02 mm at 300 Pa, and even with a clip gone it closes only 0.05 mm (0.13 mm at a panel's end). The CFD with the joint moved so gives the same moment of blow-through within 0.005 s (section 05). Between studs the Glasroc X bows in about 1.7 mm per kPa of cavity pressure, the lining sealed behind it; the section shows it.
  • Glasroc X 9 mm (LGS, 28-09-2026); the datasheets found list 12.5 mm only.
  • Contact angle 60°; wind pressure rising 4 % per metre up the wall; cladding leaks 20 mm² per m².
  • Vent openings as sharp-edged orifices, Cd 0.61; the joints themselves airtight (seal strips and water close them).
  • The LGS J-flashing's slots: 6 × 14 mm, 45 mm apart (measured by LGS).
  • Joint as built, strip in place: tests of six clip-fixed Japanese sidings (NILIM report 975, 2017) found water through the joints from about 150 Pa where the strip was not continuous; the Lab takes that for the LGS joint, with 5 mm² of gap per metre (NILIM's 1–5, leakier end).

Words used here

Rainscreen
Cladding with a drained, vented cavity behind it, so rain stops at the cladding and the wall behind stays dry.
Pressure equalisation
Letting the cavity follow the wind's pressure through vents, so the cladding's joints feel little push.
Compartment, story break
The stretch of cavity between two horizontal closures (story-break flashings); it fills and empties as one.
Starter, vented J-channel
The profiles at the foot and head of a compartment: the cavity breathes in at the starter and out through the J-channel's slots.
Lap, tongue, lip, slot, V, hairline
The shiplap edge: the lower panel's 15 mm tongue stands behind the upper panel's lip; the 1.6 mm slot between them, the V at the face and the hairline under the lip are the water's way in.
Seal strip
The factory 2.4 mm round PVC strip on the tongue, squeezed into the slot.
Contact angle
The angle a water surface meets a solid at; a low angle wets and wicks.
Field gust
A gust as measured on a real building, rising at about 4,000 Pa/s: far faster than a lab test's 3 s pulse.

Sources

  • NRC CTU-34: vent and drain holes at least 10 mm wide against bridging water.
  • Garden, CBD-40 (NRC 1963); Killip and Cheetham, Building and Environment 19(2) 1984; Baskaran, NRC IR-629 (1992).
  • Field gusts at about 4,000 Pa/s: Ganguli and Dalgliesh, J. Struct. Eng. 114(3) 1988.
  • NILIM report 975 (2017), ch. V: six clip-fixed Japanese sidings; water through the joints from about 150 Pa; fitted gaps 1–5 mm² per metre.
  • Thai wind code DPT 1311-50 (2007), required for walls by the Ministry of Interior notification of 30-08-2024; rain: Yamoat et al. (2022), Thai intensity-duration-frequency statistics.
  • Nichiha モエン standard installation guide 2026: cavity at least 12 mm, 10–15 mm open at the base flashing. Nichiha USA AWP Horizontal guide (09-2025) p. 14: metal framing of three storeys or more, a compression joint every other floor.

Check by CFD: water in the joint, OpenFOAM

OpenFOAM interFoam (volume of fluid) on the true EX joint: 39,823 cells, 0.075 mm in the joint, 60° contact angle, no seal strip, the slot prefilled to 13 mm, 0.25 s per push. Water height at the end, CFD against the Lab's engine: 115 Pa 13.8 mm (engine 13.6), 125 Pa 14.4 mm (14.4), 135 Pa 15.0 mm and still rising (engine: over the top). At 145 and 165 Pa the water reached the tongue's top and stopped at its sharp corner; none crossed into the cavity in the run. A clean, sharp corner pins the water surface and holds more than the 132 Pa the Lab's simple model gives, at least 165 Pa for 0.12 s here. A chipped, rounded or dirty corner loses that, and real gusts last longer, so the Lab keeps 132 Pa.

CFD frame: at 125 Pa the water stands 14.4 mm up the slot, below the tongue top
125 Pa, 0.25 s: the water holds at 14.4 mm, under the tongue's 15 mm top. The engine gives 14.4 mm.
CFD frame: at 165 Pa the water surface is pinned at the tongue's top corner
165 Pa, 0.25 s: 33 Pa over the 132 Pa figure, the water surface is pinned at the tongue's top corner and nothing reaches the cavity.

Modelled by LGS engineering: a physics model checked against closed-form solutions and CFD, and this page's engine checked against it case by case. Not a product test: every figure comes from a model and still needs an engineer's sign-off.

Want these numbers for your own house? Tell us about it.